Card 101

Question

What is Kirchhoff’s Voltage Law?

Answer

Kirchhoff's voltage law states that the sum of all voltages in a closed loop equals zero.

v1 + v2 + v3 + v4 = 0

In Series: Voltage is additive. (Vtotal= V1+V2...) In Parallel: Voltage is constant. (Vtotal=V1=V2...)

Card 102

Question

What is Ohm’s Law?

Answer

E=I*R

Card 103

Question

What is power factor?

Answer

Ratio of real to apparent power

Card 104

Question

What is Reactive Power (R)? What're the units?

Answer

Power that doesn't perform work- is lost to inductors and capacitors. Power Measured in Volt-Amps-Reactive.

Card 105

Question

What is Real Power (P)? What're the units?

Answer

Power used to perform work. Measured in Watts.

Card 106

Question

What is Resistance (R)? What're the units?

Answer

Measurement of opposition to current flow. Measured in Ohms.

Card 107

Question

What is the DC Power Equation?

Answer

P=I*V

Card 108

Question

What is the difference between hot, neutral, and ground?

Answer

Hot: Supply path for current.

Neutral: Return path for current.

Ground: Safety feature to eliminate shock hazards.

Card 109

Question

What is the difference between series and parallel pump operations?

Answer

Pumps in series will raise discharge pressure at a constant flow rate.

Pumps in parallel will raise flow rate at a constant discharge pressure.

Card 110

Question

What is Voltage (E)? What're the units?

Answer

Difference in electric potential between two points. Work per unit charge. Measured in Volts

Card 111

Question

What’s the difference between a positive displacement and centrifugal pump?

Answer

Positive displacement: At a given speed, pumps a volume regardless of downstream pressure.

Centrifugal Pump: At a variable speed and flow rate, will pump downstream if pressure doesn't exceed discharge pressure.

Card 112

Question

How do you escalate a medical emergency?

Answer

911 or local dispatch Immediately then escalate to building FM. 

Card 113

Question

If there is a breakdown in the escalation chain, what actions should the EOT take to escalate

Answer

Follow the escalation wiki. Continue contacting the next person on the chain until you speak to someone.

Card 114

Question

List of reasons to engage teams IE controls, FE, ATS team, Gen Team, ETC.

Answer

Controls: Emergent controls issues that cannot be solved utilizing the controls troubleshooting wiki.

FE: Tripped breaker that exceeds 32 amps. If it's urgent outside of normal business hours, cut a sev 2.5 ticket and they'll address first thing in the morning.

Maintenance teams: Contact for support in instances where specialized equipment is alarming and you've exhausted all resources in mitigating.

Card 115

Question

What actions require escalation for authorization to perform?

Answer

Closing of a tripped breaker not associated with rack down event Power cycling of EPMS units via the EPMS Troubleshooting Guides

Card 116

Question

What is the policy for critical equipment maintenance regarding: AHU/air handler Maintenance

Answer

N minimum maintained in the Pod at all times. In Pods with opposing AHUs, never have both left and right side down concurrently. No more than 2 AHUs per pod recommended to be out of service. In the Electrical rooms, only one air handler down at a time.

Card 117

Question

What is the policy for critical equipment maintenance regarding: Annual UPS/GEN maintenance

Answer

One UPS OR GEN per building at a time. Two UPS OR GEN max per AZ unless AZ is five buildings, then three of five buildings may have a single UPS OR GEN down for annual service.

Card 118

Question

What is the policy for critical equipment maintenance regarding: Battery maintenance

Answer

No more than one string out of service per UPS at any given time, per UPS, four UPS per building allowed. No more than eight strings down per AZ unless AZ is five buildings, then up to 1welve strings may be in maintenance at any given time. Include string maintenance with UPS annual service whenever possible.

Card 119

Question

What is the policy for critical equipment maintenance regarding: Controls Maintenance on EPMS

Answer

Evaluate on a case-by case basis the work, possible impact to the pod and rollback/recovery time.

Card 120

Question

What is the policy for critical equipment maintenance regarding: IR scans

Answer

No restrictions on IR scan. Observe all PPE, and restricted/exclusion zones when covers are removed.

How to use this set

Read the preview and check whether the content and answers suit your learning goal. You can add the public set to your sets to study it. Your account shows the available actions.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please reload the page.