A PID loop, or Proportional-Integral-Derivative loop, is a feedback control loop that uses three mathematical terms to adjust a control system to minimize error between a desired setpoint and a variable.
• Proportional: Produces an output value that is proportional to the current error value
• Integral: Proportional to both the magnitude and duration of the error, which is important for long-term accuracy
• Derivative: Computed based on the rate of change of the error, which can help predict future error
Basic operation of a PID loop is as follows:
• Calculate error: The PID loop calculates the error value by comparing the measured variable to the desired setpoint
• Adjust control variables: The PID loop uses the error value to adjust control variables to minimize the error
• Repeat: The output is measured again, and the process is repeated.
Card 22
Question
Discuss what readings are needed from EPMS to calculate site PUE
Answer
PUE= Total Load/IT Load
KW reading from USB Main PXM and KW reading from PDP IQ Main.
Other calcualtions for buildings without PDP boards can be found on Inframaps>Select PDX>Select Building>
Select Calculation details
Card 23
Question
Explain system activity logging and its use
Answer
System activity logging is essentially an audit trail for BMS. You can see what Action was made at what point, what date and time, if comment were made etc.
Card 24
Question
Explain the dynamic plotter and its use
Answer
Used to view trends, graphs or historical data fora point in BMS
Card 25
Question
What events can cause a PID loop to become unstable?
Answer
Too much proportional gain will result in proportional response overcorrection. This creates an unstable feedback loop.
Card 26
Question
Why is it important to know which points are in BN08?
Answer
The point in manual over ride stops BMS from automatic operation. Too many points in BN08 will effect the PID loop.
Card 27
Question
At what temperature do air handlers enter evaporative cooling mode?
Answer
Varies by site.
PDX4:
PODs - 81 degrees
ERMs - 72 degrees
Card 28
Question
Describe how failed temperature cold aisle probes affect air handler controls operations.
Answer
A probe indicating too hot will result in greater cooling being applied (during winter, this may result in subcooling).
A probe indicating too cold may result in less cooling being applied and overheating the area.
Temp sensors that have failed or are out of range will not be used in any calculations by the controllers.
A temperature sensor is considered failed or out of range if it is below 20 or above 120°F.
Card 29
Question
Describe how the air handler responds to a loss of BMS connectivity
Answer
The Air handler will default to HAND operation and determine its own mode of operation
Card 30
Question
Discuss the appropriate PPE required to perform water samples
Answer
Latex gloves and eye protection.
Card 31
Question
Discuss the effects of High or low water flow on air handler operations
Answer
High water flow will cause moisture carryover from the evaporative media into the supply air- resulting in higher humidity and lower temperatures.
Low water flow will result in inadvertent media dryout- resulting in lower humidity and higher temperatures.
Card 32
Question
Discuss the expected response for the following alarms: air handler leak alarm
Answer
Note which detector is alarming. Place machine HOA to off. Inspect area for source of water leakage and correct. Clean and dry leak detector. Remove water from area and dry. Place machine HOA to run and monitor for further leakage.
Card 33
Question
Discuss the expected response for the following alarms: air handler sump pump failure
Answer
HOA to off. Open Main disconnect. Inspect for tripped breakers or blown fuses. Before turning unit OFF, check status of motor protection overload; if it is OPEN and water level is above the low level switch, try re-energizing the pump by turning ON the motor protection switch. If the pump overload triggers again, there is likely damage to the pump, or pump wiring.
Card 34
Question
Discuss the expected response for the following alarms: Cold aisle hotspots.
Answer
Escalate, Investigate condition of Mechanical equipment supplying air in that aisle.
Deploy fans or porta coolers as needed.
Verify hot aisle containment meets standard.
Verify temp sensor in working correctly.
Card 35
Question
Discuss the expected response for the following alarms: Damper feedback mismatch
Answer
Intervention is required to investigate and take actions as necessary. Check damper wiring and functionality. If necessary, replace the damper actuator as per the O&M manual.
Card 36
Question
Discuss the expected response for the following alarms: Flood alarm
Answer
Unit must be inspected immediately as a flood may be imminent or water damage to the CRAH unit may occur. Check sensor wiring and functionality. Ensure sensor is configured for N.C. relay operation.
Card 37
Question
Discuss the expected response for the following alarms: High SAT
Answer
Shut unit off, check sump for water, check floats, bypass valve positions, damper positions, etc.
Card 38
Question
Discuss the expected response for the following alarms: High/low MAT
Answer
Shut unit off, check sump for water, check floats, bypass valve positions, damper positions, etc.
Card 39
Question
Discuss the expected response for the following alarms: CRAHU mains power lost
Answer
General: Take HOA to Off. Check all fuses, wiring, and connections. Replace faulty components as necessary.
---
Check fuses FU8 and FU9 status and wiring. Check fuses FT6 and FT5-2 status and wiring. Check relay R2 wiring and connections as well as mains power and disconnect switch status and wiring. Check fuses FU6, FU7, and FT3 status and wiring as well as PW3 connection to controller input ID15. Replace faulty devices as necessary.
Card 40
Question
Discuss the expected response for the following alarms: Purge alarm
Answer
Escalate. Investigate reason for purge condition, remedy the issue then reset purge at the purge panel.
How to use this set
Read the preview and check whether the content and answers suit your learning goal. You can add the public set to your sets to study it. Your account shows the available actions.