What is the major difference between the Eaton and Mitsubishi static switches?
Answer
Eaton carries the load through the static switch while in internal or static bypass. A Mitsubishi unit static switch carries the load until a contactor closes and then the contactor carries the load.
Card 402
Question
What will cause a UPS to automatically switch into Internal Bypass Operation?
Answer
Inverter or rectifier faults, overheating, fan failure (model specific), DC overvoltage, system overload at 106% (overload particular, depending on percentage 106-149 for 30 seconds to 10 minutes could result in a transfer. Anything 150 above is an automatic transfer).
Card 403
Question
Why do both UPSs need to be in ‘sync’ for inverter operation
Answer
Different UPS AC output frequencies would cause wave interference/cancellation. Different UPS AC output voltages would cause UPS backfeeding.
Card 404
Question
Why is it necessary to place the UPS on internal bypass before closing the MBP?
Answer
Static Bypass seamlessly switches the UPS output to Raw Utility Power (Dirty Power), allowing for a closed transition transfer