Question

What is the major difference between the Eaton and Mitsubishi static switches?

Answer

Eaton carries the load through the static switch while in internal or static bypass.  A Mitsubishi unit static switch carries the load until a contactor closes and then the contactor carries the load.

Card 402

Question

What will cause a UPS to automatically switch into Internal Bypass Operation?

Answer

Inverter or rectifier faults, overheating, fan failure (model specific), DC overvoltage, system overload at 106% (overload particular, depending on percentage 106-149 for 30 seconds to 10 minutes could result in a transfer. Anything 150 above is an automatic transfer).

Card 403

Question

Why do both UPSs need to be in ‘sync’ for inverter operation

Answer

Different UPS AC output frequencies would cause wave interference/cancellation. Different UPS AC output voltages would cause UPS backfeeding.

Card 404

Question

Why is it necessary to place the UPS on internal bypass before closing the MBP?

Answer

Static Bypass seamlessly switches the UPS output to Raw Utility Power (Dirty Power), allowing for a closed transition transfer

How to use this set

Read the preview and check whether the content and answers suit your learning goal. You can add the public set to your sets to study it. Your account shows the available actions.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please reload the page.