Card 381

Question

Describe the following as it pertains to the batteries: How are the batteries configured to make 480V

Answer

Forty twelve volt batteries are placed in series. Using Kirchhoff's Voltage Law, the sum of voltage is 480V.

Card 382

Question

Describe the following as it pertains to the batteries: How many batteries does each UPS have

Answer

40 per string @ 12VDC each.

4-5 strings per UPS.

Card 383

Question

Describe the following as it pertains to the batteries: Spill containment

Answer

Indications are battery acid in an unwanted location. Using a Spill Response Kit and associated PPE: Stop the spread. If possible, isolate the source. Clean up the spill.

Card 384

Question

Describe the following as it pertains to the batteries: Temperature requirements

Answer

Recommended temperature is between 68 and 86 degrees Fahrenheit.

Card 385

Question

Describe the following as it pertains to the batteries: What type of batteries are they

Answer

Valve Regulated Lead Acid (VRLA)

Card 386

Question

Describe the function of the following components: Inverter

Answer

UPS components which contain the equipment and controls necessary to convert input DC power to output AC power required by the critical load. This is accomplished through the use of Insulated Gate Bipolar Transistors (IGBTs) which open and close to start/stop the flow of DC current. The IGBT remains closed for longer periods of time until the the effective voltage is 480VAC. The IGBTs then begin to open in shorter incriments. This process is repeated for the negative voltage part of the AC wave and is known as Pulse Width Modulation (PWM).

Card 387

Question

Describe the function of the following components: Rectifier

Answer

UPS components which contain the equipment and controls necessary to convert input AC power to output DC power, accomplished through the use of diodes.

Card 388

Question

Describe the function of the following components: Static switch

Answer

Device which connects the critical load to the bypass line when the Inverter cannot supply continuous power

Card 389

Question

Describe what will happen If the UPS goes into Static bypass while the load is on Generator, and Utility returns.

Answer

The UPS will prevent the AMCOP from retransferring to Utility to avoid dropping the load.

Card 390

Question

Discuss the major steps of a UPS startup and shutdown

Answer

Shutting down a UPS:
Place UPS in internal bypass
Close MBP breaker
Open IOB breaker
Open MOBs
Open MIBs
Open BIBs
Open Battery breakers

Starting a UPS:
Close MIBs
Close BIBs
Start Rectifier
Start Inverter
Close Battery breakers
Close MOBs
Close IOB
Open MBP
Transfer load to Inverter

Card 391

Question

Explain the modes of operation of the UPS: Battery

Answer

UPS batteries feed the load.

Card 392

Question

Explain the modes of operation of the UPS: Internal Bypass

Answer

Incoming power feeds the load through the UPS static bypass line.

Card 393

Question

Explain the modes of operation of the UPS: Maintenance Bypass

Answer

Incoming power bypasses the UPS entirely to feed the load.

Card 394

Question

Explain the modes of operation of the UPS: Normal

Answer

Incoming utility is converted from AC to DC via a full wave rectifier. It is then converted from DC to AC via the Inverter. This is accomplished through the use of Insulated Gate Bipolar Transistors and pulse width modulation.

Card 395

Question

Roughly how long can your UPS last on batteries at full design load?

Answer

Estimated time at full load is 6-12 minutes.

Card 396

Question

State the actions taken for a loss of communications

Answer

Escalate, utilize controls troubleshooting wiki to power cycle devices if applicable. Engage Vendor.

Card 397

Question

State the actions taken for when a UPS automatically switches to Internal Bypass

Answer

Escalate, Navigate through HMI to identify fault and error codes, contact UPS Vendor via emergency contact info and provide all relevent information. Draft emergency MCM to perform a Maintenance bypass so that when the vendor arrives we can place the affected lineup on MBP to diagnose and repair UPS.

Card 398

Question

State the functions of a UPS

Answer

Provide emergency power to a load when input power source fails. Condition incoming power to provide consistent AC power to loads.

Card 399

Question

What are the 4 major brands of critical-load-maintaining UPS systems used at PDX?

Answer

Eaton, Mitsubishi, Toshiba (WMW & OPTDC), and Schneider APC

Card 400

Question

What is an IGBT and what is it for?

Answer

Insulated Gate Bipolar Transistor

Inverter in the UPS, used for converting DC to AC

How to use this set

Read the preview and check whether the content and answers suit your learning goal. You can add the public set to your sets to study it. Your account shows the available actions.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please reload the page.