Card 361

Question

What is the purpose of the House/Critical Uninterruptable Power Supply (HUPS)?

Answer

Provide stable, clean power to the HUPP/CUPP

Card 362

Question

What is the purpose of the tower beacon assembly and what do the following colors signify: Blue

Answer

Dead Bus condition

Card 363

Question

What is the purpose of the tower beacon assembly and what do the following colors signify: Green

Answer

System is in auto

Card 364

Question

What is the purpose of the tower beacon assembly and what do the following colors signify: No lights

Answer

In Manual, or light is burnt out.

Card 365

Question

What is the purpose of the tower beacon assembly and what do the following colors signify: Red

Answer

Auto Fail

Card 366

Question

What is the purpose of the tower beacon assembly and what do the following colors signify: Yellow

Answer

Load is on Generator

Card 367

Question

What is the time delay for deadbus?

Answer

90 Seconds

Card 368

Question

What two sources are considered Source 1 on a CDB ATC?

Answer

Utility power and Generator power.

Card 369

Question

What's the purpose of the SKRU?

Answer

Prevents operation of equipment out of correct sequence by electromechanically locking an operational key in place until necessary pre-requisites have been satisfied

Card 370

Question

Define the following terms and discuss their purpose: BIB

Answer

Bypass Input Breaker

Card 371

Question

Define the following terms and discuss their purpose: HUPS

Answer

House Uninterruptible Power Supply

Card 372

Question

Define the following terms and discuss their purpose: IOB/OIB

Answer

Isolation Output Breaker

Card 373

Question

Define the following terms and discuss their purpose: MBP/MBB

Answer

Maintenance Bypass Breaker

Card 374

Question

Define the following terms and discuss their purpose: MIB

Answer

Module Input Breaker

Card 375

Question

Define the following terms and discuss their purpose: MMS

Answer

Multi-Module System. When one UPS is placed onto static bypass, the other Parallel UPS also goes to static bypass.

Card 376

Question

Define the following terms and discuss their purpose: MOB

Answer

Module Output Breaker

Card 377

Question

Demonstrate proper response to various alarms eg. Failed rectifier, batteries discharging, CV2 Breaker Open.

Answer

Escalate, verify downstream loaf is stable. Navigate through HMI to identify fault and error codes, contact UPS Vendor via emergency contact info and provide all relevent information. Draft emergency MCM to perform a Maintenance bypass so that when the vendor arrives we can place the affected lineup on MBP to diagnose and repair UPS. 

Card 378

Question

Describe the following as it pertains to the batteries: Design duration to carry maximum load

Answer

Total time that UPS batteries are expected to provide power during maximum loading.

Card 379

Question

Describe the following as it pertains to the batteries: Electrical safety PPE required for work

Answer

CAT 2 and CAT 4 Arc Flash PPE, leather gloves, and safety glasses.

Card 380

Question

Describe the following as it pertains to the batteries: Full load capacity

Answer

Total amount of charge (in Amp-hours) that batteries can provide.

How to use this set

Read the preview and check whether the content and answers suit your learning goal. You can add the public set to your sets to study it. Your account shows the available actions.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please reload the page.