What is the purpose of the House/Critical Uninterruptable Power Supply (HUPS)?
Answer
Provide stable, clean power to the HUPP/CUPP
Card 362
Question
What is the purpose of the tower beacon assembly and what do the following colors signify: Blue
Answer
Dead Bus condition
Card 363
Question
What is the purpose of the tower beacon assembly and what do the following colors signify: Green
Answer
System is in auto
Card 364
Question
What is the purpose of the tower beacon assembly and what do the following colors signify: No lights
Answer
In Manual, or light is burnt out.
Card 365
Question
What is the purpose of the tower beacon assembly and what do the following colors signify: Red
Answer
Auto Fail
Card 366
Question
What is the purpose of the tower beacon assembly and what do the following colors signify: Yellow
Answer
Load is on Generator
Card 367
Question
What is the time delay for deadbus?
Answer
90 Seconds
Card 368
Question
What two sources are considered Source 1 on a CDB ATC?
Answer
Utility power and Generator power.
Card 369
Question
What's the purpose of the SKRU?
Answer
Prevents operation of equipment out of correct sequence by electromechanically locking an operational key in place until necessary pre-requisites have been satisfied
Card 370
Question
Define the following terms and discuss their purpose: BIB
Answer
Bypass Input Breaker
Card 371
Question
Define the following terms and discuss their purpose: HUPS
Answer
House Uninterruptible Power Supply
Card 372
Question
Define the following terms and discuss their purpose: IOB/OIB
Answer
Isolation Output Breaker
Card 373
Question
Define the following terms and discuss their purpose: MBP/MBB
Answer
Maintenance Bypass Breaker
Card 374
Question
Define the following terms and discuss their purpose: MIB
Answer
Module Input Breaker
Card 375
Question
Define the following terms and discuss their purpose: MMS
Answer
Multi-Module System. When one UPS is placed onto static bypass, the other Parallel UPS also goes to static bypass.
Card 376
Question
Define the following terms and discuss their purpose: MOB
Answer
Module Output Breaker
Card 377
Question
Demonstrate proper response to various alarms eg. Failed rectifier, batteries discharging, CV2 Breaker Open.
Answer
Escalate, verify downstream loaf is stable. Navigate through HMI to identify fault and error codes, contact UPS Vendor via emergency contact info and provide all relevent information. Draft emergency MCM to perform a Maintenance bypass so that when the vendor arrives we can place the affected lineup on MBP to diagnose and repair UPS.
Card 378
Question
Describe the following as it pertains to the batteries: Design duration to carry maximum load
Answer
Total time that UPS batteries are expected to provide power during maximum loading.
Card 379
Question
Describe the following as it pertains to the batteries: Electrical safety PPE required for work
Answer
CAT 2 and CAT 4 Arc Flash PPE, leather gloves, and safety glasses.
Card 380
Question
Describe the following as it pertains to the batteries: Full load capacity
Answer
Total amount of charge (in Amp-hours) that batteries can provide.
How to use this set