Card 341

Question

What equipment does the Mechanical Service Distribution Board (MSDB) serve?

Answer

ER Exhaust Fans

DH Exhaust Fans

DH Air Handlers

Generator

ICW Pumps

MV Switchgear

Card 342

Question

What equipment does the Office Lighting Power Panel (OLP) serve?

Answer

Office lighting, exterior lighting, and disk destruction devices.

Card 343

Question

What equipment does the Office Mechanical Power Panel (OMP) serve?

Answer

Office Mechanical HVAC equipment for heating and cooling. TU's and EHU's

Card 344

Question

What equipment does the Office Power Panel (OPP) serve?

Answer

Office outlets, exterior outlets, disk degausser, security equipment

Card 345

Question

What information do you need and whose permission is required to reset a breaker

Answer

Breaker ampergage is required. If over 32A, Field Engineering must approve. Under 32A allow for a single reset before escalating to Field Engineering.

Card 346

Question

What is a breaker trip unit?

Answer

Part of a circuit breaker that opens the circuit in the event of a thermal overload, short circuit, or ground fault

Card 347

Question

What is a PQM? What is its relationship with the AMCOP?

Answer

Power Quality Meter is a device suitable for monitoring and recording of power quality. It measures, monitors, and records harmonics, sags, swells, flickers and other power quality parameters.

At Who Made Who (WMW) sites, when the Amazon Change-Over Panel (AMCOP) receives an input from the upstream power quality meter indicating excessive (>12%) vTHD on the utility source, AMCOP initiates and completes a transfer to generator, and then auto-fails.

Card 348

Question

What is a sectionalizing switch?

Answer

MV lineup isolations. Can be used to align either MV SWGR 'A' or 'B' to a series of electrical rooms.

Card 349

Question

What is an AMCOP Auto Fail condition?

Answer

Autofail is an AMCOP condition defined by one of the following:

• Automatic operation has failed or fault has occurred

• Automatic transfer is interrupted

• Operator intervention is required to return the system to normal

Card 350

Question

What is an auto-fail and how can it be reset when the issue is corrected?

Answer

Autofail is an AMCOP condition defined by one of the following:

• Automatic operation has failed or fault has occurred

• Automatic transfer is interrupted

• Operator intervention is required to return the system to normal

After the cause is investigated and corrected:

•Turn the mode selector switch from AUTO to OFF/RESET

• Acknowledge the auto fail condition on the HMI

• Return the mode selector switch to AUTO

Card 351

Question

What is an HRG and how does it work?

Answer

A resistor that connects a neutral point to ground, allowing for the detection of ground faults. Once a fault is detected, it can be located and selectively tripped so upstream equipment may remain unaffected and in operation.

Card 352

Question

What is Fast Loop Restoration Scheme (FLoRES)?

Answer

FLoRES is an automated protection system that automatically detects and isolates electrical faults within 5-10 cycles and restores voltage to the unaffected sections within seconds or less.

Card 353

Question

What is the function of the Basler relay? What are it's tolerances?

Answer

"Eyes" of the AMCOP, reports health of power for Generator and Utility. Acceptable ranges are +/- 10%Voltage, +/-4.2% Frequency

Card 354

Question

What is the function of the CDB ATC

Answer

Transfer Critical Load to source 2

Card 355

Question

What is the power source for the 24VDC shunt trip inside the power distribution cabinet (PDC)?

Answer

BACOP

Card 356

Question

What is the purpose of dynamic load balancing in the Catcher Output Panels (COPs)?

Answer

Utilize the redundant Catchers to full capacity, prevent overloading, and maintain redundancy. The system monitors the load flow at the Catcher system and sends control commands (open/ close) to the COP main circuit breakers to switch the loads between the two Catchers and configure the system loads as required.

Card 357

Question

What is the purpose of the blue indicator light on the Power Distribution Cabinet (PDC)?

Answer

Identify if a BACOP Shunt Trip has been activated.

Card 358

Question

What is the purpose of the catcher distribution system?

Answer

To provide alternative power to critical load in the event the primary source(s) are not available.

Card 359

Question

What is the purpose of the catcher lineup and how is it different from a USB lineup?

Answer

Catcher provides a zone defense for a single USB lineup across multiple electric rooms.

Card 360

Question

What is the purpose of the generator E-stop that is located on the switchgear?

Answer

To provide a means of remotely emergency stopping a generator.

How to use this set

Read the preview and check whether the content and answers suit your learning goal. You can add the public set to your sets to study it. Your account shows the available actions.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please reload the page.