Cards in this set

Card 161

Question

Define the following terms: Standby Generator

Answer

A secondary power source available if utility power experiences faults/inconsistencies/failure

Card 162

Question

Define the following terms as it relates to the Generator: Stop Mode

Answer

A manual mode that emergency stops the generator without a cool-down period

Card 163

Question

Define what the EMCP is and its importance to the generator

Answer

Electronic Modular Control Panel. Provides the interface for controlling the generator.

Card 164

Question

Discuss how the battery system works

Answer

The batteries are for the starter motor, to get the generator running. The battery system has 2 12 VDC batteries wired in series which are in parallel to 2 12 VDC batteries wired in series. This results in 4 batteries total.

Card 165

Question

Discuss how to verify that the enclosure louvers are operating as designed

Answer

During generator confidence tests, a visual inspection during the initial ramp up and the cool down of the generator will show the functionality of the louvers (opening and closing).

Card 166

Question

Discuss how to verify whether air filters are healthy or require replacing

Answer

There is a differential pressure gauge on top of the filters that will show a red indicator when the differential pressure has surpassed a preferred ratio, thus showing that the filters need changing.

Card 167

Question

Discuss normal operating parameters of a generator under load

Answer

Coolant temperature (<208 F)

oil pressure (>40 psi)

speed (1795-1805 RPM)

frequency (59-61 Hz)

amperage (0 A if unloaded)

voltage (475-485 V).

Card 168

Question

Discuss the different ways to switch the generator to the off position

Answer

Press "Stop" On the EMCP, Press E-stop, Open output CB. AMCOP > Mode selector > Manual > Generator start > OFF

Card 169

Question

Discuss the expected indications and response to the following casualties: Excessive exhaust smoke

Answer

If the line-up is on generator than the EOT should leave the generator as is. It is more important to keep the customers service operational and let the generator overheat. Amazon may have to pay an environmental fine and/or pay to fix/replace a generator but the customer comes first. If found during gen run exercises, escalate, stop gen exercise for that generator and engage the Gen team.

Card 170

Question

Discuss the expected indications and response to the following casualties: Fuel/oil/coolant spill

Answer

Indications are fuel/oil/coolant in an unwanted location. Using a Spill Response Kit and associated PPE: Stop the spread (apply drain covers and barriers). Stop potential ignition sources. If possible, isolate the source. Clean up the spill.

Card 171

Question

Discuss the expected indications and response to the following casualties: Generator output breaker tripping

Answer

-If generator is not carrying load, escalate. -If generator is carrying load, verify loads (racks and mechanical) transfer to alternate power supply. For sites equipped with a USB catcher system, verify Deadbus timer is fulfilled and ATC transfers load to 480V Catcher. Once load stability has been validated, escalate.

Card 172

Question

Discuss the expected indications and response to the following casualties: Generator high engine temperature

Answer

Escalate to On-all Manager, call the FOC and get a TT cut, notify Gen team. Await permissions for actions or until qualified engineer/ tech arrives on site to assess.

Card 173

Question

Discuss the expected indications and response to the following casualties: Generator low oil pressure

Answer

Escalate to On-all Manager, call the FOC and get a TT cut, notify Gen team. Await permissions for actions or until qualified engineer/ tech arrives on site to assess.

Card 174

Question

Discuss the expected indications and response to the following casualties: Generator low voltage output.

Answer

Basler relay will read low voltage (10% discrepancy) and will perform an open transition back to utility or put the line-up on battery if utility is unavailable at which point DCEO could put the entire line-up on catcher via the ATC 600 to prevent exhausting all battery power.

Card 175

Question

Discuss the expected indications and response to the following casualties: Generator low water jacket temperature

Answer

Indications are a low coolant temperature alarm. Escalate and contact the Gen Team for support.

Additional inspections: Verify heater is functioning and coolant is flowing. If heater is off or coolant isn't flowing, verify breaker positions (power panel and customer panel) are closed. Verify heater contact is operating normally. Inspect all associated wiring for damage or indications of electrical fire. If there are signs of an electrical fire, open associated breakers to secure power.

Card 176

Question

Discuss the expected indications and response to the following casualties: Over crank condition

Answer

Escalate to On-all Manager, call the FOC and get a TT cut, notify Gen team. Await permissions for actions or until qualified engineer/ tech arrives on site to assess.

Card 177

Question

Discuss the expected indications and response to the following casualties: Generator over speed condition.

Answer

Escalate to On-all Manager, call the FOC and get a TT cut, notify Gen team. Await permissions for actions or until qualified engineer/ tech arrives on site to assess.

Card 178

Question

Discuss the expected indications and response to the following casualties: PLC/AMCOP failure

Answer

The system will maintain current configuration and will be unable to provide automated response.

Card 179

Question

Discuss the expected indications and response to the following casualties: USB main generator breaker failing to close when commanded

Answer

AMCOP will go into AUTOFAIL.

If utility is available, load retransferred to Utility. Verify loads (racks and mechanical) are operating normally. Reset AUTOFAIL.

If utility is unavailable, verify loads (racks and mechanical) transfer to alternate power supply.

For sites equipped with a USB catcher system, verify Deadbus timer is fulfilled and ATC transfers load to 480V Catcher. Once load stability has been validated, escalate.

Card 180

Question

Discuss the expected indications and response to the following casualties: USB main generator breaker failing to open when commanded

Answer

AMCOP will go into AUTOFAIL.

If generator is available, load remains on generator. Verify loads (racks and mechanical) are operating normally. Reset AUTOFAIL.

If generator is unavailable, verify loads (racks and mechanical) transfer to alternate power supply.

For sites equipped with a USB catcher system, verify Deadbus timer is fulfilled and ATC transfers load to 480V Catcher. Once load stability has been validated, escalate.

How to use this set

Read the preview and check whether the content and answers suit your learning goal. You can add the public set to your sets to study it. Your account shows the available actions.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please reload the page.