Discuss the expected indications and response to the following casualties: USB main generator breaker tripping
Answer
AMCOP will go into AUTOFAIL.
If generator is not carrying load, escalate.
If generator is carrying load and utility is available, load is transferred to utility. Verify loads (racks and mechanical) are operating normally. Reset AUTOFAIL.
If generator is carrying load and utility is unavailable, verify loads (racks and mechanical) transfer to alternate power supply.
For sites equipped with a USB catcher system, verify Deadbus timer is fulfilled and ATC transfers load to 480V Catcher. Once load stability has been validated, escalate.
Card 182
Question
Discuss the expected indications and response to the following casualties: USB main utility breaker failing to close when commanded
Answer
AMCOP will go into AUTOFAIL.
If generator is available, load is transferred back to generator. Verify loads (racks and mechanical) are operating normally. Reset AUTOFAIL.
If generator is unavailable, verify loads (racks and mechanical) transfer to alternate power supply.
For sites equipped with a USB catcher system, verify Deadbus timer is fulfilled and ATC transfers load to 480V Catcher.
Once load stability has been validated, escalate.
Card 183
Question
Discuss the expected indications and response to the following casualties: USB main utility breaker failing to open when commanded
Answer
AMCOP will go into AUTOFAIL.
If utility is available, load remains on utility. Verify loads (racks and mechanical) are operating normally. Reset AUTOFAIL.
If utility is unavailable, verify loads (racks and mechanical) transfer to alternate power supply.
For sites equipped with a USB catcher system, verify Deadbus timer is fulfilled and ATC transfers load to 480V Catcher. Once load stability has been validated, escalate.
Card 184
Question
Explain how to fuel the generator including PPE and spill containment requirements
Answer
Generators are refueled through vendor contact and scheduling. DCEO are required to verify tank levels post fueling.
For sites with digital level indicators, read the indicator.
For sites without level indicators, the tanks must be dipped. Dipping tanks requires hearing protection, eye protection, and nitrile gloves.
Card 185
Question
Explain how to identify proper coolant level
Answer
The glass cylinder above the generator fan that indicates the coolant level. If coolant is visible, then the coolant levels are appropriate.
Card 186
Question
Explain how to manually operate the generator and utility breakers in the switchgear
Answer
AMCOP > Mode Selector > Manual > Generator start > ON > Verify voltage/Hz > AMCOP HMI > Transfer load to generator (Open Utility breaker/Close generator breaker) AMCOP > Mode selector > Manual > Generator start > ON > Verify voltage/Hz > Switchboard > Open MCBU > Close MCBG
Card 187
Question
Explain how to manually run the generator without placing it on the utility bus
Explain how to verify that the Generator coolant heater and thermostat are operating correctly
Answer
On the Generator HMI an EOT will be able to see what the coolant temperature is. The coolant temperature should be above 90F (preferably above 100F).
Card 189
Question
Explain how to verify the oil level is in its normal operating band
Answer
Using the dipstick > take dipstick out > clean off > re-insert dipstick back in to get an accurate measurement of the levels > read whether the oil is too high or too low based on the dipstick markings. There are two sides- one for running, one for off.
Card 190
Question
Explain the different ways to switch the generator to automatic controls
Answer
At EMCP: Reset (if E-stopped, pull out E-stop) > AUTO button
At AMCOP: AMCOP > mode selector > AUTO > Generator start > OFF
Card 191
Question
State the KW rating of the generators
Answer
KW rating will vary for site or PERDIX.
PDX4 standard is 2000Kw (2MW)
Card 192
Question
What does a flashing amber LED Light on the Generator EMCP indicate?
Answer
Generator is in a warning condition, will still start but needs to be addressed.
Card 193
Question
What does a Red LED light on the Generator EMCP indicate?
Answer
Generator is in shutdown mode due to a critical fault. Must be placed into stop to reset and could potentially have tripped the Output breaker depending on the fault.
Card 194
Question
What's acceptable coolant temperature when our generators aren't running?
Answer
90 - 130 Degrees
Card 195
Question
What's the normal position of the CAM Breaker? Temp Gen/LB Switch? What does the Temp Gen/Load Bank Switch do?
Answer
Breaker Normally Open.
Switch in Gen/Load Bank Position.
When switch is switched to Temp Gen it changes the source of 24 volt DC from the permanent gen to the temp gen. Changing the 24vdc signal from the start/run relay for permanent gen to the start/run relay for the temp gen. Esentially ensuring that AMCOP is controlling the temp Gen as needed.
Card 196
Question
Define what legionella is and why it is harmful to personnel
Answer
Bacteria which causes lung infections such as Legionnaires' disease and Pontiac fever.
Card 197
Question
Describe how water gets to the PERDIX
Answer
Utility water enters ICW for chemical treatment and then enters the PERDIX.
Card 198
Question
Discuss the purpose of the UV skids and how they work
Answer
UltraViolet Light (UV Light) is used to disinfect the water system of germs, viruses, mold, bacteria, and fungi. This is accomplished by exposing the water to UV Light waves.
Card 199
Question
Discuss the steps taken to monitor and control Legionella in the data center.
Answer
Vendors perform cyclic sampling and analysis of sumps. Samples which test above desired levels result in machine remediation. Machine remediation involves opening machine supply fan breakers to prevent air flow, adding treatment chemicals to the sump, and forcing the machine into evaporating cooling to circulate the chemicals.
Card 200
Question
How frequently do we dump the evaporative cooler sumps?
Answer
Varies by site. PDX4 is every 7 days.