How many gallons of water do you hold in your water tanks? How many tanks?
Answer
Varies by site. PDX4 is 2 x 40,200 gallons and 2 x 51,000 gallons
Card 202
Question
How would you respond to the following alarm: Low system supply water pressure (Loss of water)
Answer
Verify proper pump operation. Verify adequate tank levels (if low, check proper skid operations). Verify proper valve lineups for supplying water. Perform rounds on potentially affected equipment.
Card 203
Question
How would you respond to the following alarm: Storage tank low level alarm
Answer
Verify tank level. Verify skid operations. If skid is tripped, determine and correct cause. If weekly flushing and dumping is occurring, monitor tank levels. Verify proper valve lineups for supplying water. Perform rounds on potentially affected equipment.
Card 204
Question
Piping ruptures in the WT/RO system to include: Downstream of permeate side of skid
Answer
Shut closest upstream and downstream valves to isolate rupture. Verify proper operation of standby skid. Perform rounds on potentially affected equipment.
Card 205
Question
Piping ruptures in the WT/RO system to include: Upstream of skid, downstream of ICW inlet valve
Answer
Shut closest upstream and downstream valves to isolate rupture. Verify proper operation of standby skid. Perform rounds on potentially affected equipment.
Card 206
Question
What is reverse osmosis and why is it preferred?
Answer
Reverse Osmosis is a form of water purification that uses pressure applied to "dirty" water. This drives the water molecules across a semi-permeable membrane while leaving contaminants behind. The result is an almost pure water.
Card 207
Question
What is the purpose of the water tanks and where are they filled from?
Answer
For some sites, Water tanks are a redundant water source in the event that we lose city water. Water tanks are filled from our city water source.
For other sites, water tanks are where treated water is stored before building use.
Card 208
Question
Where are the Industrial Waste Water lift station pumps located?
Answer
Varies by site. PDX4 located in front of loading dock.
Card 209
Question
Where are the in-ground industrial cooling water isolation valve located?
Answer
Varies by site. PDX4 located in front of main security building.
Card 210
Question
Where is the Industrial Waste Water lift station located?
Answer
Varies by site. PDX4 located in front of loading dock.
Card 211
Question
Why do we flush the evaporative media and at what frequency?
Answer
Quarterly to remove impurity build up (improves efficiency).
Card 212
Question
Answer the following regarding rackdown events: How would you respond to a TOR Failure?
Answer
Place Splinter in Pending, Work of DCO Master Workflow. Mark Rack with visual indicator (see it on both sides). Follow Work Flow to troubleshoot bad TOR, Power Drain, Proceed to Storm Rack while TOR is powering back up, grab replacement TOR from Storm Rack, if services haven't recovered, follow work flow to replace TOR.
Card 213
Question
Answer the following regarding rackdown events: Name the different ways personnel are notified of a rackdown
Answer
Via E-mail, Alarm via shift phone, SIM ticket, Rackdown slack channel.
Card 214
Question
Answer the following regarding rackdown events: What is a rackdown?
Answer
An EBS or EC2 rack with 25% or more hosts lost.
Card 215
Question
Answer the following regarding rackdown events: What is a the purpose of DCEO Rackdown Ticket?
Answer
Notification and tracking.
Card 216
Question
Answer the following regarding rackdown events: What is the rackdown workflow?
Answer
Interactive rack troubleshooting and restoration procedure.
Card 217
Question
Answer the following regarding rackdown events: What is the typical rack down ticket severity and why?
Answer
SEV 2 to prioritize rack restoration. SLA of 45 minutes to meet promise of 99.999% up time.
Card 218
Question
Answer the following regarding rackdown events: Which racks will we lose if an IOB or PDP breaker trips? What will happen to EC2 and Networking Racks?
Answer
All Single Source (Prod) Racks will go offline.
N+C's will transfer to Catcher.
2N's will swing load onto their other source (A or B).
Card 219
Question
Define the following power redundancies: 2N
Answer
Twice what is necessary.
Card 220
Question
Define the following power redundancies: C2N
Answer
Twice what is necessary plus a catcher (zone defense).