Back to overview

PDX DCEO Qualification Card

Discover PDX DCEO Qualification Card: 404 flashcards with questions and answers.

Subject
No category / Others
Language of creation
English
404 flashcards No ratings yet 0 views
Add to my sets

Sign in to add this set to your collection. You will return here afterwards.

Cards in this set

Card 261

Question

What voltage is the bus bar for the Who Made Who Rack/WAIPOUA/YELM/OPAL?

Answer

12VDC

Card 262

Question

Where do the two sources come from for a rack ATS?

Answer

Utility & Catcher

Card 263

Question

Where do you find your PDT rack count?

Answer

PDT AHA but you need logical access. DCO can typically help as they usually have logical access.

Card 264

Question

Where is the EPMS server located?

Answer

Site Specific. Refer to controls wiki system information tab.

Card 265

Question

Whose permission is required to replace an ATS?

Answer

If it is a Sev2 scenario, then permission to replace an ATS is automatically granted in the event that not replacing the ATS will continue to impact customers.

Otherwise; on-call manager, CE, FM (or higher).

Card 266

Question

Describe what an arc flash is?

Answer

An arc flash is the intense light and heat produced by an electrical arc.

This violent release of energy at extreme temperatures can be a source of damage to equipment, personnel injury, and/or death.

Card 267

Question

Describe what forms of energy are we concerned about for LOTO?

Answer

Any form of hazardous energy. Electrical, Hydraulic, Kinetic, etc.

Card 268

Question

Explain at what point is arc flash an issue?

Answer

Anytime you break the plane of exposure within a piece of gear or remove a protection measure (like a deadfront panel) with intentions of working on the gear.

Card 269

Question

Explain how to inspect Insulating gloves?

Answer

Air test before each days use. Check for pin holes, cracking, cuts, contaminant or embedded wire.

Card 270

Question

Explain how to perform a dead check (Live-Dead-Live)?

Answer

Test multi-meter on a known good source, check equipment to be serviced, recheck multi-meter on known good source. Try and start equipment

Card 271

Question

Explain how you would find out what potential the arc flash could be?

Answer

Coordination study, tag on the front of the equipment

Card 272

Question

Explain the importance of wearing leather protectors over your rubber gloves.

Answer

Provides protection of electrical insulation equipment against cuts, rips, nicks, etc...

Card 273

Question

Explain the lock out tag out (LOTO) procedure and discuss why it is needed.

Answer

Shutdown equipment, isolate from all types of energy and apply lockout/tagout, release stored energy and verify state (drain/depressurize/deenergize), verify isolation/lockout, perform work, verify equipment is safe to restore, remove lockout/tagout, restore equipment to usual state.

Card 274

Question

Explain what a limited approach boundary is?

Answer

For use with Arc Flash boundaries. No unqualified persons may enter this area unless escorted by a qualified person with the understanding of the hazards present.

Card 275

Question

Explain what a restricted approach boundary is?

Answer

No qualified person shall enter the restricted approach boundary unless they are in PPE. Requires EEWP.

Card 276

Question

Explain what an Arc Flash Boundary is?

Answer

The distance at which the incident energy equals 1.2 cal. May not enter the arc flash boundary unless trained on the hazards and wearing the required PPE.

Card 277

Question

Explain what SDS is and where to find it?

Answer

Safety Data Sheet.

Card 278

Question

Explain what the concern is with ARC Flash/blast?

Answer

Explosive force behind it and how it could kill or severely hurt someone.

Card 279

Question

Explain what the difference is between arc flash PPE and electrical shock PPE?

Answer

Arc flash PPE is arc rated but is not rated for electrical shock protection (i.e. 40 cal suit) 

Electrical shock protection is based on electrical insulation properties and is rated by the voltage level it protects against (i.e. Class 0 rated rubber gloves good up to 1000 volts).

Card 280

Question

Explain what the hierarchy of control is?

Answer

Least effective to most effective. PPE, admin controls, awareness, engineering controls, substitution, elimination

How to use this set

Read the preview and check whether the content and answers suit your learning goal. You can add the public set to your sets to study it. Your account shows the available actions.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please reload the page.