Discuss the following with regard to the switchgear HMI/AMCOP: Discuss what happens if both main line power sources are lost to the switchgear HMI/AMCOP
Answer
AMCOP will enter an Auto Fail condition. A Deadbus timer will start. If supply power has not been restored once the timer is complete (90 seconds) the ATC (Woodward) will transition so load is provided via 480V Catcher.
Card 302
Question
Discuss the following with regard to the switchgear HMI/AMCOP: List the components that interface with the switchgear HMI/AMCOP
Answer
Associated MCBU, MCBG, generator, utility Basler, generator Basler, and BMS.
Card 303
Question
Discuss the following with regard to the switchgear HMI/AMCOP: List the power supplies for the switchgear HMI/AMCOP
Answer
HPP, HUPP/CUPP, internal battery
Card 304
Question
Discuss the following with regard to the switchgear HMI/AMCOP: What busses do the basler relays monitor?
Answer
Upstream of MCBU and MCBG (Utility and Generator busways)
Card 305
Question
Discuss the following with regard to the switchgear HMI/AMCOP: What is the difference between the basler relays and the interposing relays?
Answer
A basler relay is considered the "eyes" for the PLC, they look for anomalies and notify the PLC. The Interposing relays are considered "the hands" for the PLC, they are used to carry out automatic functions as dictated by the PLC.
Card 306
Question
Discuss the reasons for long time, short time, instantaneous, and ground fault settings
Answer
Long: Overload Protection
Short: Delayed short-circuit Protection
Instantaneous: Instant short-circuit Protection
Ground Fault: Short-circuit to ground protection
Card 307
Question
During an Emergency can you perform breaker manipulation by yourself?
Answer
Yes, but it is not recommended. Use EOP and escalate.
Card 308
Question
Explain how power is distributed from medium voltage transformer to the rack.
Explain the controls inside the power distribution cabinet (PDC).
Answer
PDCs contain the following: surge and short circuit protection devices to protect downstream WMW racks. Meters for monitoring cabinet current, power, temperature, and line to line voltage. Redundant internal device power supply. BACOP integration units.
Card 310
Question
Explain the different breaker rack out positions (connected, test, disconnected, and withdrawn)
Answer
Connected: Power (Primary), Control (Secondary/Auxiliary) circuits, and ground are connected, breaker is racked in and fully operational.
Test: Power (Primary) circuit is disconnected with Control (Secondary/Auxiliary) circuit and ground connected, breaker is operational for offline testing and safety.
Disconnected: Power (Primary), Control (Secondary/Auxiliary) circuits are disconnected, ground is connected. Breaker is partially racked out offline.
Withdrawn: Power (Primary), Control (Secondary/Auxiliary) circuits, and ground are disconnected, breaker is fully racked out and offline.
Card 311
Question
Explain what happens when the MCBG breaker trips with the Generator supplying all loads.
Answer
AMCOP will enter an Auto Fail condition. A Deadbus timer will start. If supply power has not been restored once the timer is complete (90 seconds) the ATC (Woodward) will transition so load is provided via 480V Catcher.
Card 312
Question
Explain why we have a coordination study performed for our electrical distribution system.
Answer
Coordination studies are useful for determining selective tripping guidelines. This provides the ability to sequentially trip loading on the lowest possible levels and limit adjacent customer impact.
Card 313
Question
How do you perform an OPTDC USB to Catcher Tie?
Answer
Rack out/disconnect MCBU and MCBG, complete a deadbus timer, use SKRU key to close MCBC
Card 314
Question
How does the backstopping system (BACOP) work?
Answer
BACOP senses busway loading and preemptively sheds loading selectively to protect critical loads and circuit breakers.
Card 315
Question
How does the FLoRES work?
Answer
FLoReS communicates between adjacent protection relays in loops to automatically isolate electrical faults within 5-10 cycles and restore voltage to the unaffected sections within seconds. Fault indication is via 2 Feeder Protection Relays or 1 Transformer Protection Relay.
Card 316
Question
How is a breaker trip indicated?
Answer
Local indicator and EPMS.
Card 317
Question
How long can the Critical Uninterruptible Power Supply (CUPS) supply its loads while on battery?
Answer
Depends on loading. Average loading (<10%) is in excess of 60 minutes.
PDX4 is roughly 6-12 minutes.
Card 318
Question
If a utility outage were to occur, explain how the 6A lineup would respond.
Answer
Customer load is carried via UPS batteries (non-WMW) or powershelf batteries (WMW). WMW sites will additionally use UPS batteries to power mechanical loads. Basler relays detect a loss of utility. After 3 seconds, the utility breaker opens and the generator is started. After a 12 second (5 seconds for WMW sites) stabilization delay, the generator breaker is closed and the generator supports customer load.
Card 319
Question
In relation to the ATC what does TDNE and TDEN stand for?
Answer
TDNE = Time delay normal to emergency. TDEN = Time delay emergency to normal.
Card 320
Question
List the control power sources for the USB and PDP
Answer
Utility, Generator, HUPP and associated UPS.
OPTDC: Utility, Generator, CUPP A, and CUPP B,